Skip to product information
1 of 1

PF 18

VAA-4E4A-KE5-ZEJQ/R / PF 269780 - AS-Interface module

VAA-4E4A-KE5-ZEJQ/R / PF 269780 - AS-Interface module

Regular price $438.98 NZD
Regular price Sale price $438.98 NZD
Sale Sold out
Shipping calculated at checkout.

Price (exc. GST) each

AS-Interface module, VAA-4E4A-KE5-ZEJQ/R / PF 269780

  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Selectable supply to the sensors: External or from the module
  • Function display for bus, internal sensor supply, inputs, and outputs

Details: VAA-4E4A-KE5-ZEJQ/R / PF 269780 

Cabinet module, 4 inputs and 4 relay outputs

Compatible Part Numbers:

269780 

VAA-4E4A-KE5-ZEJQ/R

Technical Data Sheet:

Datasheet excerpt: Technical data of  VAA-4E4A-KE5-ZEJQ/R / PF 269780

General specifications
Node type Standard node
AS-Interface specification V3.0
Required gateway specification ≥ V2.0
UL File Number E223772
MTBF 224 a
Indicators/operating means
LED FAULT Fault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INT Internal input supply active; LED green
LED PWR AS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED IN switching state (input); 4 LED yellow
LED OUT Switching state (output); 4 LED yellow
Electrical specifications
Auxiliary voltage (input) 12 ... 30 V DC PELV
Rated operating voltage 26.5 ... 31.6 V from AS-Interface
Rated operating current ≤ 35 mA (without sensors) / max. 230 mA
Surge protection O1 ... O4: Over voltage category II
UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type 4 inputs for 3-wire sensors (PNP), DC
Supply from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage 21 ... 31 V DC (INT)
Current loading capacity ≤ 150 mA, overload- and short-circuit protected (INT)
Input current ≤ 5.6 mA (max.)
Switching point according to DIN EN 61131-2 (type 1)
0 (unattenuated) ≤ 0.5 mA
1 (attenuated) ≥ 2 mA
Signal delay < 1 ms (input/AS-Interface)
Output
Number/Type 4 relay outputs, normally open
Supply none
Nominal load
Per contact 2 A/30 VDC; 2 A/250 VAC
For more information, see the "Galvanic Isolation" section
Per module 8 A
Control circuit ≤ 11 mA per relay (from AS-Interface)
Switching delay < 10 ms (AS-Interface/contact)
Usage category DC-13 and AC-14
Switching
Mechanical 5 x 107
Electrical 2 x 105 (250 VAC, 2 A, cos φ = 0.4)
Galvanic isolation
Input/Output safe isolation, Rated insulation voltage 252 Veff
Input/AS-Interface Switch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff
Output/Output Basic insulation, rated insulation voltage 250 Veff, in phase
Output/AS-Interface safe isolation, Rated insulation voltage 252 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Low voltage
Directive 2006/95/EC EN 60664-1:2007
Standard conformity
Galvanic isolation EN 60664-1:2007
Degree of protection EN 60529:2000
Fieldbus standard EN 62026-2:2013
Electrical safety IEC 61140:2009
Input EN 61131-2:2004
Emitted interference EN 61000-6-4:2007
AS-Interface EN 62026-2:2013
Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013
Programming instructions
Profile S-7.0
IO code 7
ID code 0
ID1 code F
ID2 code E
Data bits (function via AS-Interface) InputOutput
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 O4
Parameter bits (programmable via AS-i) function
P0 Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1 Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2 Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
P3 not used
Ambient conditions
Ambient temperature -25 ... 60 °C (-13 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Relative humidity 85 % , noncondensing
Climatic conditions For indoor use only
Altitude ≤ 2000 m above MSL
Shock and impact resistance 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree 2
Mechanical specifications
Degree of protection IP20
Installation in an enclosure with a minimum protection class of IP54 required
Connection Removable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
Housing PA 66-FR
Mass 125 g
Dimensions
Height 100 mm
Width 18.9 mm
Length 124 mm
Mounting DIN mounting rail

 

Classifications

System Classcode
ECLASS 13.0 27242604
ECLASS 12.0 27242604
ECLASS 11.0 27242604
ECLASS 10.0.1 27242604
ECLASS 9.0 27242604
ECLASS 8.0 27242604
ECLASS 5.1 27242604
ETIM 9.0 EC001599
ETIM 8.0 EC001599
ETIM 7.0 EC001599
ETIM 6.0 EC001599
ETIM 5.0 EC001599
UNSPSC 12.1 39121535

2 in stock