1
/
of
3
PF 61
KFD2-EB2.R4A.B - PF 189784 - Power Feed Module (Redundant) 143567
KFD2-EB2.R4A.B - PF 189784 - Power Feed Module (Redundant) 143567
Regular price
$406.50 NZD
Regular price
Sale price
$406.50 NZD
Unit price
/
per
Shipping calculated at checkout.
Price (exc. GST) each
Couldn't load pickup availability
Power Feed Module (Redundant), KFD2-EB2.R4A.B - PF 189784
- Interface for Power Rail
- Used for redundant configuration
- Supply current ≤ 4 A
- Replaceable fuse
- Relay contact output, reversible
- LED status indication
Details: KFD2-EB2.R4A.B - PF 189784
Power rail interface, plastic housing, 24 V DC operating voltage, max. 4 A supply current, replaceable fuse, relay contact output, screw terminals.
Part Numbers:
189784
KFD2-EB2.R4A.B
Technical Data Sheet:
Datasheet excerpt: Technical data of KFD2-EB2.R4A.B - PF 189784
| Output | |
| Connection | Power Rail |
| Output current | max. 4 A |
| Output voltage |
Ui ≥ rated voltage Ur = Ui - 0.6 V
|
| Fault signal |
relay output: NO contact
|
| Contact loading |
30 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
|
| Energized/De-energized delay |
approx. 20 ms / approx. 20 ms
|
| Indicators/settings | |
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling |
space for labeling at the front
|
| Directive conformity | |
|
Electromagnetic compatibility
|
|
| Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations)
|
| Conformity | |
| Electromagnetic compatibility | NE 21:2017 |
| Degree of protection | IEC 60529:2001 |
| Ambient conditions | |
| Ambient temperature |
-40 ... 60 °C (-40 ... 140 °F) (extended ambient temperature range up to 70 °C [158 °F], refer to manual for necessary mounting conditions)
|
| Mechanical specifications | |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D), housing type B2
|
| Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001
|
|
Data for application in connection with hazardous areas
|
|
| Certificate |
UL 22 ATEX 2853 X
|
| Marking |
II 3G Ex ec nC IIC T4 Gc
|
| Directive conformity | |
| Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN IEC 60079-15:2019
|
| International approvals | |
| FM approval |
FM 22 US 0031 X
|
| Control drawing | 116-0160 |
| UL approval | E106378 |
| CSA approval | CoC 1051840 |
| IECEx approval | |
| IECEx certificate |
IECEx UL 16.0051X
|
| IECEx marking |
Ex ec nC IIC T4 Gc
|
1 in stock
Share